W415-0244 / A / 05.15.03
INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com [email protected]
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.22, AND ANSI Z21.50 RESPECTIVELY FOR VENTED GAS FIREPLACES.
DIRECT VENT MILLIVOLT SYSTEM
INSTALLATION AND OPERATION INSTRUCTIONS FOR
DIRECT VENT DECORATIVE GAS FIREPLACE
NATURAL GAS MODEL
BGD38NT
PROPANE GAS MODEL
BGD38PT
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS
Installation and service must be performed by a qualified installer, service agency
or the gas supplier.
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from
a neighbour's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier,
call the fire department.
Page view 0
1 2 3 4 5 6 ... 27 28

Summary of Contents

Page 1 - DIRECT VENT MILLIVOLT SYSTEM

1W415-0244 / A / 05.15.03INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON

Page 2 - TABLE of CONTENTS

10W415-0244 / A / 05.15.03H2H1V190°when (Ht) > (Vt)Simple venting configuration (only one90° elbow)See graph to determine the required ver-tical ri

Page 3

11W415-0244 / A / 05.15.03Example 4:V1=5 ftV2=10 ftVT=V1 + V2 = 5 + 10 = 15 ftH1=1 ftH2=3 ftH3=2.5 ftHR= H1 + H2 + H3 = 1 + 3 + 2.5 = 6.5 ftHO= .03(fo

Page 4 - GENERAL INFORMATION

12W415-0244 / A / 05.15.03Formula 1: HT < 3VTFormula 2: HT + VT < 40 feetExample 5:V1=2 ftV2=1 ftV3=1.5 ftSee graph to determine the required v

Page 5 - VENTING LENGTHS

13W415-0244 / A / 05.15.03This application occurswhen venting through aroof. Installation kits forvarious roof pitches areavailable from your Na-poleo

Page 6 - AIR TERMINAL INSTALLATIONS

14W415-0244 / A / 05.15.03Use only approved aluminum flexi-ble liner kits marked:"Wolf Steel Approved Venting" as identified by thestamp on

Page 7 - SPECIAL VENT INSTALLATIONS

15W415-0244 / A / 05.15.03FIGURE 25The vent system must be supported approximately every 3feet for both vertical and horizontal runs. Use Wolf Steelve

Page 8

16W415-0244 / A / 05.15.03Proceed once the vent installation is complete.1. Move the fireplace into position and secure using thenailing tabs and/or s

Page 9 - DEFINITIONS

17W415-0244 / A / 05.15.03It is not necessary to install a hearth extension with thisfireplace system.Note: In order to avoid the possibility of expos

Page 10

18W415-0244 / A / 05.15.03Lift up and remove the upperlouvres. Open the valve controldoor. Release the top and bot-tom door latches, located at therig

Page 11 - TOP EXIT VERTICAL TERMINATION

19W415-0244 / A / 05.15.03Remove the backing of thelogo supplied and place on theglass viewing door, asindicated.½"½"LOGOFIGURE 39PHAZERTM l

Page 12

2W415-0244 / A / 05.15.03WARNING••••• Do not burn wood or other materials in this fireplace.• Adults and especially children should be alerted to the

Page 13 - WALL AND CEILING PROTECTION

20W415-0244 / A / 05.15.03INSTALLATION TO BE DONE BY A QUALIFIED IN-STALLER and must be electrically connected and groundedin accordance with local co

Page 14 - W415-0244 / A / 05.15.03

21W415-0244 / A / 05.15.03ELECTRICAL INSTALLATION TO BE DONE BY A QUALI-FIED INSTALLER and must be connected and groundedin accordance with local code

Page 15 - USING RIGID VENT COMPONENTS

22W415-0244 / A / 05.15.03GAS KNOBPILOTHIOLPOFFLOPINOLOTFFOWhen lit for the first time, the fireplace will emit a slightodour for a few hours. This is

Page 16

23W415-0244 / A / 05.15.03Closing the air shutter will cause a more yellow flame, butcan lead to carboning.Opening the air shutter will cause a more b

Page 17 - NAILING TABS

24W415-0244 / A / 05.15.03# PART NO. DESCRIPTION34* W175-0166 5" COUPLER34* W175-0002 8" COUPLER35 GDLVK LOUVRE KIT - UPPER & LOWER - BL

Page 18 - FINISHING

25W415-0244 / A / 05.15.03* WARNING: This is a fast acting thermocouple. It is an integral safety component. Replace only witha fast acting thermocoup

Page 19 - LOGO PLACEMENT

26W415-0244 / A / 05.15.03Pilot will not light. - check if pilot can be lit by a match- check that the wire is connected to the push button ignitor.

Page 20 - OPTIONAL BLOWER INSTALLATION

27W415-0244 / A / 05.15.03White / grey filmforms.Sulphur from fuel is beingdeposited on glass, logs orcombustion chamber sur-faces.- clean the glass

Page 21 - OPTIONAL FAN INSTALLATION

28W415-0244 / A / 05.15.03Wolf Steel Fireplace Service HistoryThis fireplace must be serviced annually depending on usage.DateService Technician NameS

Page 22 - OPERATION / MAINTENANCE

3W415-0244 / A / 05.15.03ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS

Page 23 - ADJUSTMENTS

4W415-0244 / A / 05.15.03THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERV-ICED BY A QUALIFIED INSTALLER to conform with local codes.Installation pract

Page 24 - REPLACEMENTS

5W415-0244 / A / 05.15.03Use only Wolf Steel or Simpson Dura-Vent Model DV-GSventing components. Minimum and maximum vent lengths,for both horizontal

Page 25

6W415-0244 / A / 05.15.03AIR TERMINAL INSTALLATIONS*** Recommended to prevent condensation on windows and thermal breakage********** It is r

Page 26 - TROUBLE SHOOTING GUIDE

7W415-0244 / A / 05.15.03Use the GD401 periscope kit to locate the air terminationabove grade. The periscope must be installed so that whenfinal gradi

Page 27 - SYMPTOM PROBLEM TEST SOLUTION

8W415-0244 / A / 05.15.03VERVERVERVERVERTICALTICALTICALTICALTICALTERMINTERMINTERMINTERMINTERMINAAAAATIONTIONTIONTIONTIONHORIZONTHORIZONTHORIZONTHORIZO

Page 28 - Service Technician

9W415-0244 / A / 05.15.03for the following symbols used in the venting calcula-tions and examples are:> - greater than> - equal to or greater th

Related models: BGD38NT