1W415-0429 / C / 11.04.05INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON
10W415-0429 / C / 11.04.05Example 4:V1=5 ftV2= 10 ftVT=V1 + V2 = 5 + 10 = 15 ftH1=1 ftH2=3 ftH3= 2.5 ftHR= H1 + H2 + H3 = 1 + 3 + 2.5 = 6.5 ftHO= .03(
11W415-0429 / C / 11.04.05Formula 1: HT < 3VTFormula 2: HT + VT < 40 feetExample 5:V1=2 ftV2=1 ftV3= 1.5 ftSee graph to determine the required
12W415-0429 / C / 11.04.05FIGURE 15This application oc-curs when ventingthrough a roof. Installa-tion kits for various roofpitches are availablefrom y
13W415-0429 / C / 11.04.05Use only approved aluminum flexi-ble liner kits marked:"Wolf Steel Approved Venting" as identified by thestamp o
14W415-0429 / C / 11.04.05FIGURE 25The vent system must be supported approximately every 3feet for both vertical and horizontal runs. Use Wolf Steelve
15W415-0429 / C / 11.04.05Proceed once the vent installation is complete.1. Move the fireplace into position and secure using thenailing tabs and/or s
16W415-0429 / C / 11.04.0537 3/4"6"17 3/4"INSIDECHASE37 3/4"40 1/8"56 3/4"37 3/4"39 1/4"17 3/4"7"4&
17W415-0429 / C / 11.04.05Lift up and remove the upperlouvres. Open the valve controldoor. Release the top and bot-tom door latches, located at therig
18W415-0429 / C / 11.04.054. Place the bottom of log #6 against the right side of thefirebox. The upper branch rests against log #1. The lowerbranch r
19W415-0429 / C / 11.04.05FIGURE 467. Remove the flame effect panel by removing the 6 screws.8. Remove the flame generator by sliding to the left andd
2W415-0429 / C / 11.04.05WARNING• Do not burn wood or other materials in this fireplace.• Adults and especially children should be alerted to the haza
20W415-0429 / C / 11.04.051. Turns electric flame on/off.2. Turns gas flame on/off.3. Activates gas flame adjustment.4. Activates fan adjustment.5. Ad
21W415-0429 / C / 11.04.05• Turn off all gas to the fireplace.• Open windows.• Do not try to light any appliance.• Do not touch any electric switch; d
22W415-0429 / C / 11.04.05This fireplace requires 6 amps, 120 volt and a 60 hzgrounded circuit.Do NOT use the fireplace if any part has been underwate
23W415-0429 / B / 05.25.04Adjust the pilot screw to provide properly sized flame. Turnin a clockwise direction to reduce the gas flow.Air shutters hav
24W415-0429 / C / 11.04.05GD220 (5 FT)# PART NO. DESCRIPTION37* W010-0397 4" FLEXIBLE ALUMINIUM LINER - (5 FT ) C/W SPACERS37* W410-0017 7"
25W415-0429 / C / 11.04.0548454446471213*161411552221396650516059ATTENTION-CHAUDCAUTION - HOT402AUTOON/OFFMANUALON/OFFFlameFanTimerClock24272826734516
26W415-0429 / C / 11.04.05Pilot will not light. - check if pilot can be lit by a match- check that the wire is connected to the push button ignitor.
27W415-0429 / C / 11.04.05Remote control - Dead batteries. - Make sure batteries are charged.not working - No power to the unit. - Make sure main powe
28W415-0429 / C / 11.04.05Excessive noise - Flame generator motor is - Consult your local dealer.coming from the unit. faulty.Odour - Initial curing p
3W415-0429 / C / 11.04.05ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS
4W415-0429 / C / 11.04.05THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERV-ICED BY A QUALIFIED INSTALLER to conform with local codes.Installation pract
5W415-0429 / C / 11.04.05Use only Wolf Steel or Simpson Dura-Vent Model DV-GSventing components. Minimum and maximum vent lengths,for both horizontal
6W415-0429 / C / 11.04.05AIR TERMINAL INSTALLATIONS***** Recommended to prevent condensation on windows and thermal breakage********** It is
7W415-0429 / C / 11.04.05Use the GD201 periscope kit to locate the air terminationabove grade. The periscope must be installed so that whenfinal gradi
8W415-0429 / C / 11.04.05for the following symbols used in the venting calcula-tions and examples are:> - greater than> - equal to or greater th
9W415-0429 / C / 11.04.05H2H1V190°when (Ht) > (Vt)Simple venting configuration (only one90° elbow)See graph to determine the required ver-tical ris