1W415-0299 / F / 01.16.07
10W415-0299 / F / 01.16.07REQUIREDVERTICALRISE IN FEET(VT)CALCULATED HORIZONTAL VENT RUNPLUS OFFSETS IN FEET (HT)FIGURE 545ºFIGURE 690°H1H2when (HT) &
11W415-0299 / F / 01.16.07See graph to determine the re-quired vertical rise VT for the requiredhorizontal run HT.For vent configurations requiring mo
12W415-0299 / F / 01.16.07Example 3:V1=5 ftV2= 10 ftVT=V1 + V2 = 5 + 10 = 15 ftH1=3 ftH2= 2.5 ftHR= H1 + H2 = 3 + 2.5 = 5.5 ftHO= .03(one 45º elbow +
13W415-0299 / F / 01.16.07For vent configurations requiring more than one 45º andone 90° elbow , the following formulas apply:Formula 1: HT < 3VTF
14W415-0299 / F / 01.16.07FIGURE 15When finishing the fireplace, combustible material mayrest directly on of the top extension.Note: Maximum weight to
15W415-0299 / F / 01.16.07Combustible materials may be installed flush with the frontof the fireplace but must not cover any of the black face-areas o
16W415-0299 / F / 01.16.07Refer to pages 6-13. All venting must have a minimumclearance of 1" to combustible.See Page 18 for additional framing d
17W415-0299 / F / 01.16.07Refer to pages 6-13. All venting must have a minimumclearance of 1" to combustible.See Page 18 for additional framing d
18W415-0299 / F / 01.16.07There must be a minimum of 1" clearance to combustibleswhen framing around all venting options. See pages 10-13.FIGURE
19W415-0299 / F / 01.16.07FIGURE 321010FIGURE 30For optimum performance it is recommended that allhorizontal runs have a minimum 1/4 inch rise per foo
2W415-0299 / F / 01.16.07Pg 3-5 INTRODUCTIONWarrantyGeneral InstructionsGeneral InformationCare of Glass & Plated PartsDimensions 6-13 VENTINGVent
20W415-0299 / F / 01.16.07AIR TERMINALCONNECTORINNER FLEXLINEROUTER FLEXLINERINNER SLEEVEHIGHTEMPERATURESEALANTROOF SUPPORTFor safe and proper operati
21W415-0299 / F / 01.16.07STORM COLLARFLASHINGCAULKINGWEATHER SEALANT2”AIR INLETBASEFIGURE 391. Install the 5 inch diameter aluminum flexible liner
22W415-0299 / F / 01.16.07TOP OF THE UNITTOP EXTENTION7" MANTLE3" MANTLE*COMBUSTIBLE MATERIALSFIRESTOP SPACERSTUD3"7"1"Combus
23W415-0299 / F / 01.16.07PHAZERTM logs, glowing and charcoal embers, exclusiveto Napoleon fireplaces, provide a unique and realistic glow-ing effect
24W415-0299 / F / 01.16.07L36 LOUVRE INSTALLATIONFIGURE 54 a-cHOODAttach the hood by pressing thetop flange into the clips alongthe top of the louvre
25W415-0299 / F / 01.16.07Ensure that thedoor is properlyclipped onto thesteel lip to pre-vent overheat-ing, glass break-age and / or dis-colouration
26W415-0299 / F / 01.16.07Remove the "Z" shapedmounting bracket securedto the burner, by the pilot.Remove the thermodiscfrom the bracket su
27W415-0299 / F / 01.16.07system and any gas control which hasbeen under water.• Turn off all gas to the fireplace.• Open windows.• Do not try to ligh
28W415-0299 / F / 01.16.07Adjust the pilot screw to provide properly sized flame. Turnin a clockwise direction to reduce the gas flow.Natural gas mode
29W415-0299 / F / 01.16.07# PART No. DESCRIPTION1* W361-0016 GLOWING EMBERS2* W550-0001 CHARCOAL EMBERS3* W562-0009 DOOR GASKET (100 INCHES)4 W010-04
3W415-0299 / F / 01.16.07NAPOLEON products are manufactured under the strict Standard of the world recognizedISO 9001 : 2000 Quality Assurance Certifi
30W415-0299 / F / 01.16.07* WARNING: This is a fast acting thermocouple. It is an integral safety component.Replace only with a fast acting thermocoup
31W415-0299 / F / 01.16.07# PART No. DESCRIPTION1 W690-0001 MILLIVOLT THERMOSTAT2 GD501 HEAT GUARD3* W573-0007 HI-TEMP SEALANT4* W010-0370 WALL SUPPOR
32W415-0299 / F / 01.16.07Carbon is beingdeposited onglass, logs orcombustionchamber sur-faces.Flame is impinging on thelogs or combustion cham-ber.-
33W415-0299 / F / 01.16.07Main burner goesout; pilot goes out.Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"Vent is blocked- check for ven
34W415-0299 / F / 01.16.07Wolf Steel Fireplace Service HistoryThis fireplace must be serviced annually depending on usage.DateService Technician NameS
35W415-0299 / F / 01.16.07NO TES
36W415-0299 / F / 01.16.07NO TES
4W415-0299 / F / 01.16.07THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICEDBY A QUALIFIED INSTALLER to conform with local codes.Installation practic
5W415-0299 / F / 01.16.07DIMENSIONSSEE-THRUPENINSULAOPEN-ENDFIGURE 1aFIGURE 1bFIGURE 1c
6W415-0299 / F / 01.16.07Use only Wolf Steel or Simpson Dura-Vent Model DV-GS,Selkirk Direct Temp or American Metal Ameriventventing components. Minim
7W415-0299 / F / 01.16.07***** Recommended to prevent condensation on windows and thermal breakage********** It is recommended to use a heat shield an
8W415-0299 / F / 01.16.07VENTING APPLICATION FLOWCHARTVE R TICALTERMINATIONHORIZONTALTERMINATIONvertical riseis equal toor greaterthan thehorizontalru
9W415-0299 / F / 01.16.0740 FEETMAXIMUM34 INCHESMINIMUMUse the GD401 periscope kit to locate the air terminationabove grade. The periscope must be ins