1W415-0153 / B / 06.10.10INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.INSTALLATION AND OPERATIN
10W415-0153 / B / 06.10.103.1 VENTING LENGTHS AND COMPONENTSUse only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or
11W415-0153 / B / 06.10.103.2 TYPICAL VENT INSTALLATION26 3/4"16" MINIMUM40 FEET MAXIMUM 3'MINIMUM26 3/4"29" MINIMUM 55 3/4&
12W415-0153 / B / 06.10.10Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading
13W415-0153 / B / 06.10.103.4 VENT TERMINAL CLEARANCESINSTALLATIONSCANADA U.S.A.A 12” 12” Clearance above grade, veranda porch, deck or balcony.B 12”
14W415-0153 / B / 06.10.103.6 DEFINITIONS14.1For the following symbols used in the venting calculations and examples are:> - greater than> - equ
15W415-0153 / B / 06.10.103.8 TOP EXIT HORIZONTAL TERMINATION16.1ASimple venting confi guration (only one 90° elbow)(HT) < (VT)For vent confi gurati
16W415-0153 / B / 06.10.10(HT) > (VT) Simple venting configuration (only one 90° elbow)See graph to determine the required vertical rise VT for the
17W415-0153 / B / 06.10.103.9 TOP EXIT VERTICAL TERMINATION(HT) < (VT) Simple venting configurations.See graph to determine the required vertical
18W415-0153 / B / 06.10.10(HT) > (VT) Simple venting configurations.See graph to determine the required vertical rise VT for the required horizonta
19W415-0153 / B / 06.10.103.10 VERTICAL THROUGH EXISTING CHIMNEYThis appliance is designed to be attached to a 3" co-linear fl exible vent system
2W415-0153 / B / 06.10.10NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.TABLE OF CONTENTS1.0 INSTALLATION OVERVIEW
20W415-0153 / B / 06.10.104.0 INSTALLATION!WARNINGFOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS EXACTLY.ALL INNER EX
21W415-0153 / B / 06.10.104.2 WALL AND CEILING PROTECTIONFor optimum performance, it is recommended that all horizontal runs have a minimum 1/4"
22W415-0153 / B / 06.10.104.2.2 VERTICAL INSTALLATIONThis application occurs when venting through a roof. Installation kits for various roof pitches a
23W415-0153 / B / 06.10.104.2.4 VERTICAL AIR TERMINAL INSTALLATIONA. Fasten the roof support to the roof using the screws provided. The roof support
24W415-0153 / B / 06.10.10A. Attach the adjustable pipe to the last section of rigid pipe. Secure with screws and seal.B. Install the inner fl ex pip
25W415-0153 / B / 06.10.104.5 GAS INSTALLATION30.1AInstallation and servicing to be done by a qualifi ed installer. Do not use open fl ame.• Move the a
26W415-0153 / B / 06.10.104.7 B-VENT SPECIFICS4.7.1 CHIMNEY INSTALLATION63.7“A” VENT - SOLID FUEL WOOD BURNING CHIMNEY & VENT CONNECTOR(LINER NEED
27W415-0153 / B / 06.10.104.7.2 INSTALLING "B" VENTFollow the instructions of the "B" vent manufacturer for chimney installation.A
28W415-0153 / B / 06.10.104.7.5 ADDING VENT SECTIONSAdd chimney sections, according to the manufacturers installation instructions. The chimney must e
29W415-0153 / B / 06.10.105.0 FINISHING5.1 DOOR CLOSING AND OPENING!WARNINGRISK OF FIRE!NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE. DO NOT STR
3W415-0153 / B / 06.10.10Door, see “DOOR CLOSING / OPENING” section.Rating plate, see “RATING PLATE” section.Logo, see “LOGO PLACEMENT” section.Vent,
30W415-0153 / B / 06.10.105.2.1 Place the back log into the fi rebox, pushing it as close to the fi rebox wall as possible and centered onto the log su
31W415-0153 / B / 06.10.105.5 LOGO PLACEMENTRemove the backing of the logo supplied and centre over the logo installation holes, as indicated.5.3 GLOW
32W415-0153 / B / 06.10.106.0 OPERATIONMODEL GS28 ONLY: SPILL SWITCHThis is a thermally activated switch, attached to the back of the chimney adaptor,
33W415-0153 / B / 06.10.106.1 OPERATING/LIGHTING INSTRUCTIONSThe on-off switch is located on the back of the unit at the top left corner on models GDS
34W415-0153 / B / 06.10.107.0 ADJUSTMENT7.1 PILOT BURNER ADJUSTMENTAdjust the pilot screw to provide properly sized fl ame. Turn in a clockwise direct
35W415-0153 / B / 06.10.107.3 FLAME CHARACTERISTICSIt’s important to periodically perform a visual check of the pilot and burner fl ames. Compare them
36W415-0153 / B / 06.10.108.0 MAINTENANCECAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
37W415-0153 / B / 06.10.108.2 BLOWER REPLACEMENTBlower replacement may be done through either the fi rebox or from the rear of the unit. Using the rear
38W415-0153 / B / 06.10.109.0 REPLACEMENTSContact your dealer or the factory for questions concerning prices and policies on replacement parts. Normal
39W415-0153 / B / 06.10.10COMMON COMPONENTSREF NO. PART NO. DESCRIPTION26* W380-0002 VARIABLE SPEED SWITCH KNOB27 KB-35 VARIABLE SPEED SWITCH28 GZ552
4W415-0153 / B / 06.10.103.1A!WARNING• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.• Do not operate appliance before
40W415-0153 / B / 06.10.10ROOF TERMINAL KITSREF NO. PART NO. DESCRIPTIONGD112 - ROOF TERMINAL KIT - FLAT ROOF47 W490-0073 4/7 INNER/OUTER SLEEVE48 W67
41W415-0153 / B / 06.10.1028PIPILOTNOLOTHILOFFO45671327293012141613152522231083435363739394043424545454564474849505152 534658323162
42W415-0153 / B / 06.10.1010.0 TROUBLE SHOOTINGSYMPTOM PROBLEM TEST SOLUTIONMain burner goes out; pilot stays on.Pilot fl ame is not large enough or no
43W415-0153 / B / 06.10.10SYMPTOM PROBLEM TEST SOLUTIONPilot will not light. No spark at pilot burner. - Check if pilot can be lit by a match. - Chec
44W415-0153 / B / 06.10.10SYMPTOM PROBLEM TEST SOLUTIONMain burner goes out; pilot stays on.Venting is spilling. - Test with spill switch bypassed.
45W415-0153 / B / 06.10.10 NAPOLEON® warrants its products against manufacturing defects to the original purchaser only. Registering your warranty is
46W415-0153 / B / 06.10.1012.0 SERVICE HISTORY43.1
47W415-0153 / B / 06.10.1044.113.0 NOTES
48W415-0153 / B / 06.10.1044.1
5W415-0153 / B / 06.10.102.1 DIMENSIONS22 1/2”11 1/4”26 3/4”7” Ø AIR INTAKE4” Ø FLUE18 1/2”5 1/2”17 3/4”12”10”GAS LINE ACCESS HOLE LOCATED IN PEDESTAL
6W415-0153 / B / 06.10.104.1THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation pra
7W415-0153 / B / 06.10.102.3 GENERAL INFORMATIONGDS28 GS28NG LP NG LPAltitude (FT) 0-4,500 0-4500 0-4500 0-4500Max. Input (BTU/HR) 30,000 26,000 30,00
8W415-0153 / B / 06.10.10INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the model, venting and
9W415-0153 / B / 06.10.103.0 VENTING7.1THIS APPLIANCE USES A 4” EXHAUST / 7” AIR INTAKE VENT PIPE SYSTEM.Refer to the section applicable to your insta