* Within the appliance enclosure a 6” (152mm) clearance between the top of the vent pipe and combustible
materials is required. All other clearances within the enclosure, including where the vent pipe exits the enclo-
sure are subject to 2” (51mm) to the sides and bottom and 3” (76mm) to the top for horizontal and 1” (25mm)
for vertical.
** See venting section.
IMPORTANT: The LHD50 requires a minimum inside enclosure height of 60” (1524mm), measured from the
bottom of the appliance. For temperature requirements, this area must be left unobstructed. It is recommended
that the enclosure be ventilated at the top and bottom to circulate the hot air.
Before nishing in the appliance test the operation using the remote control, cycling it through all of its different
modes, see “OPERATION” section. Check pressure readings, see “PILOT BURNER ADJUSTMENT” section.
Once nished in, access to the control components can only be done through the inside of the appliance.
5.3 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
!
WARNING
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THESE MATERIALS NEVER OVERHANG
INTO THE APPLIANCE OPENING.
60"
1524mm
MINIMUM
ENCLOSURE
HEIGHT
TOP OF
APPLIANCE
OPENING
32"
813mm
MINIMUM
28"
711mm
MINIMUM
COMBUSTIBLE
MATERIAL
NON-COMBUSTIBLE
STEEL STUD
FRAME
COMBUSTIBLE
NON-COMBUSTIBLE
TOP OF ENCLOSURE
NOTE: JOINT COMPOUNDS AND TAPES THAT ARE RESILIENT
TO HEAT AND CRACKING SHOULD BE USED WHEN TAPING
AND MUDDING SEAMS.
6"
152mm *
0” IF NON-COMBUSTIBLE
FINISHING IS USED SUCH
AS BRICK AND STONE.
3"
76mm
2"
51mm
51"
1295mm
MINIMUM
PLUS RISE**
9"
229mm
TO SIDEWALL