Napoleon-fireplaces Vector 45 - LHD45 User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 120
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
W415-0834 / E / 06.13.13
13
EN
13.1A
TOP EXIT
Horizontal Termination
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12.2m)
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
Horizontal run +
vertical rise to
Horizontal run +
vertical rise to
4.2 times the
vertical rise equal to
or greater than the
horizontal run
3 times the vertical
rise equal to or
greater than the
horizontal run
maximum of 40 feet
(12.2m)
maximum of 40 feet
(12.2m)
3.5 VENT APPLICATION FLOW CHART
14.1
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H
T
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
H
R
- combined horizontal vent lengths in feet
H
O
- offset factor: .03 (total degrees of offset - 90°*) in feet
V
T
- combined vertical vent lengths in feet
15.1A
FEET INCHES MILLIMETERS
0.03 0.5 12.7
15° 0.45 6.0 152.4
30° 0.9 11.0 279.4
45° 1.35 16.0 406.4
90°* 2.7 32.0 812.8
* The rst 90° offset has a zero value and is shown in the formula as - 90°
NOTE: There MUST be a 25% reduction in total horizontal length (H
T
) when using ex vent.
3.6 DEFINITIONS
3.7 ELBOW VENT LENGTH VALUES
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 119 120

Comments to this Manuals

No comments